Item | S3800E |
V/F control | |
Control mode | Sensorless flux vector control (VC) |
Cloed-loop vector control(CVC) | |
Vextor control :0~320Hz | |
Maximum frequency | V/F control :0~3200Hz |
Dgital setting :0.01Hz | |
Input frequency esolution | Analog setting :0.025% of maximum frequency |
G type :0.5Hz/150%; 0 Hz/ 180%(CLVC) | |
Startup torque | P type :0.5Hz/100% |
1:100(SFVC) | |
Speed range | 1:1000(CLVC) |
Speed stability accuracy | ±0.2%(CLVC) |
±0.5%(SFVC) ± 0.02%(CLVC) | |
Torque control accuracy | ±5%(CLVC) |
Overload capacity | G type : 60s for 150% of the rated current, 3s for 180% of the rated current |
P type : 60s for 120% of the rated current, 3s for 150% of the rated curren | |
Torque boost | Auto boost |
Customized boost 0.1%-30.0% | |
V/F curve | Multi-point curve |
N-power V/F curve (1.2 power ,1.4 power,1.6 power,1.8power,square ) | |
V/F separation | Two types :complete separation ; half separation |
Ramp mode | Straight-line ramp |
S-curve ramp | |
Four groups of acceleration /deceleration time with the range of 0.0.-6500s | |
DC braking | DC braking frequency :0.00HZ to maximun frequency |
Braking time :0.0~100.0s | |
Braking action current value :0.0%- 100.0% | |
JOG control | JOG frequency range :0.00~ 50.00HZ |
JOG acceleration /deceleration time :0.0~ 6500.0s | |
Onboard multiple preset speeds | It implements up to 16 speeds via the simple PLC function or combination of terminal states |
Onboard PID | It realizes process-controlled closed loop control system easily |
Auto voltage Regulation (AVR) | It can keep constant output voltage automatically when the mains voltage changes. |
Overvoltage /Overcurrent stall control | The current and voltage are limited automatically during the running process so as to avoid frequenct tripping due to overvoltage /over current |
Torque limit and control | It can limit torque automatically and prevent frequent over current tripping during the running process .Torque control can be implemented in the CVC mode |
Support for the multiple PG card | Support for rotating transformer PD card , differential input PG card, resolver PG card and OC input PG card |
Power dip ride through | Reduction so that the AC drive can continue to run for a short time |
Rapid current limit | It helps to avoid frequent over current faults of the AC drive |
High performance | Control of asynchronous motor and synchronous motor are implemented through the high -performance current vector control technology . |
Timing control | Time range : 0.0~ 6500.0 mintes |
Communication Methods | MODBUS -RTU \ PROFIBUS -DP\ CAN |
Protection mode | Motor short -circuit detection at power -on , input/output phase loss protection ,over current protection, overvoltage protection, under voltage protection , overheat protection and overload protection |
Installtion Location | Indoor , free from direct sunlight , dust , corrosive gas, combustible gas, oil smol, vapour , drip or salt |
Altitude | Lower than 1000m |
Ambient temperature | -10-40de-rated if the ambient temperature is between 40 and 50 |
Storage temperture | -20~60 |
In Stock
S3800
S3800E Series Closed-loop vector control – High performance: Control of asynchronous motor and synchronous motor are implemented through the high-performance current vector control technology.
Overload capacity 60s for 150% of the rated current, 3s for 180%( 120%) of the rated current.
Ramp mode: Straight-line ramp; S-curve ramp; Four groups of acceleration/deceleration time with the range of 0.0–6500.0s
Category: PLC, Drive, HMI