Main control fuctions Maximum frequency Vector control: 0~600Hz
VF control:0~1200Hz
Carrier Frequency 1k ~ 15kHz; the carrier frequency will be automatically adjusted according to the load characteristics.
Input frequency Digital setting: 0.01Hz
resolution Analog setting: maximum frequency ×0.1%
Control mode Open loop vector control ;
V/F control.
Start-up torque Mode G machine: 0.5Hz/180% (open loop vector control)
Mode P machine: 0.5Hz/120% (Open loop vector control)
Speed adjustment 1:200(Open loop Vector flux control)
range
Main control fuctions Stable speed Open loop Vector flux control:≤±0.5% (rated synchronous speed)
Precision
Stabilization of Open loop Vector flux control:≤±0.3% (rated synchronous speed)
speed control
Torque response ≤40ms(Open magnetic flux vector control)
Overload capacity Mode G machine: 150% rated current 60s; 180% rated current 5s
Mode P machine: 130% rated current 60s; 150% rated current 5s
Torque boost Automatic torque boost; manual torque boost 0.1% to 30.0%
V/F curve Linear V/F, Multi-point V/F, and Square V/F
Speed-up and Speed-down curve Straight line or S curve speed-up and speed-down mode;
four kinds of speed-up and speed-down time;
Speed-up and speed-down time ranges from 0.0s
to 3000.0s
DC brake DC brake frequency: 0.00Hz ~ maximum frequency; brake time: 0.0s ~ 36.0s, and brake current value: 0.0% to 100.0%.
Jog control Jog frequency range:0.00Hz ~ 50.00Hz;
Jog speed-up/speed-down time: 0.0s ~ 3000.0s.
Simple PLC and multi-speed running It can realize a maximum of 16 segments speed running via the built-in PLC or control terminal.
Built-in PID It is easy to realize process-controlled close loop control system.
(AVR)Automatic It can keep constant output voltage automatically in case of change of mains voltage.
voltage regulation
Torque limit and control “Shovel” characteristics, automatic limit on the torque on running time, preventing frequent over-current trip; closed loop vector mode can realize the torque control
Customized fuctions Peripherals self-detection upon It can conduct safety detections on the peripherals upon power-on, including earth and short circuit detections.
power-on
Shared DC bus It can realize the function that multiple inverters share the DC bus.
function
JOG key Programmable key: Select the forward and reverse rotations/jog operation command.
Customized fuctions Traverse frequency control Multiple triangular-wave frequency control function.
Fast current limit function With fast current limit algorithm built in to reduce the probability of over-current alarm; to improve the anti-jamming capacity of the whole machine.
Timed control Timing control function: Setting time range from 0h to 65535h.
Keyboard extension line standardization Customers can use standard cable to extend the keyboard
Operation function Running command Three types of channels: operation panel given, control terminal given and serial communication port given. These channels can be switched in various ways.
channel
Frequency source Ten types of frequency sources in total: digital given, analog voltage given, analog current given, pulse given, and serial port given. It can be switched in various ways.
Auxiliary frequency source Ten types of auxiliary frequency sources in total. It can implement micro tuning and synthesis of auxiliary frequency.
Input terminal Five digital input terminals, and seven terminals in maximum (AI1, AI2 can be used as DI terminals), it has compatibility to PNP or NPN input method.
Two analog input terminals, in which AI1 only be used for voltage input, and AI2 can be used as voltage or current input. (if expanded- input or output terminal function is needed, please use M700 series.)
Output terminal One digital output terminal (bipolar output)
Two relay output terminal
Two analog output terminals, with optional 0/4mA to 20mA or 0/2V to 10V. It can realize the output of set frequency, output frequency and rotation speed etc.
Display and Keyboard Operate LED display Display parameter
LCD display Selective parts, Chinese/English to suggest the operation content
Parameter copy Use parameter special copy keyboard can copy the parameter quickly
Key lock and function choose Lock part of the keyboard or the whole keyboard, definite the function range of some keys to avoid mis-operation.
Protection and select accessories protection function Short circuit detective of power-on motor, input and output open-phase protection, over-current protection, overvoltage protection, under-voltage protection, over-heat protection, over-load protection etc.
Selective accessories LCD operation panel, brake group etc.
Environment Suitable place Indoor environment which is against from direct sunlight, dust, corrosive gas, combustible gas, oil mist, vapor, water drop and salt.
Altitude Less than 1000m
Ambient Temperature -10ºC ~ +50ºC (derating is required if the natural temperature range is 40ºC ~ 50ºC)
Humidity Less than 95%RH, no condensing water drops
Vibration Less than 5.9m/ s2 (0.6g)
Storage temperature -20ºC ~ +60ºC
Class of pollution 2
Product Safety standard IEC61800-5-1:2007
standard EMC standard IEC61800-3:2005