| Item | M500 | |
| Main control fuctions | Maximum frequency | Vector control: 0~600Hz |
| VF control:0~1200Hz | ||
| Carrier Frequency | 1k ~ 15kHz; the carrier frequency will be automatically adjusted according to the load characteristics. | |
| Input frequency | Digital setting: 0.01Hz | |
| resolution | Analog setting: maximum frequency ×0.1% | |
| Control mode | Open loop vector control ; | |
| V/F control. | ||
| Start-up torque | Mode G machine: 0.5Hz/180% (open loop vector control) | |
| Mode P machine: 0.5Hz/120% (Open loop vector control) | ||
| Speed adjustment | 1:200(Open loop Vector flux control) | |
| range | ||
| Main control fuctions | Stable speed | Open loop Vector flux control:≤±0.5% (rated synchronous speed) |
| Precision | ||
| Stabilization of | Open loop Vector flux control:≤±0.3% (rated synchronous speed) | |
| speed control | ||
| Torque response | ≤40ms(Open magnetic flux vector control) | |
| Overload capacity | Mode G machine: 150% rated current 60s; 180% rated current 5s | |
| Mode P machine: 130% rated current 60s; 150% rated current 5s | ||
| Torque boost | Automatic torque boost; manual torque boost 0.1% to 30.0% | |
| V/F curve | Linear V/F, Multi-point V/F, and Square V/F | |
| Speed-up and Speed-down curve | Straight line or S curve speed-up and speed-down mode; | |
| four kinds of speed-up and speed-down time; | ||
| Speed-up and speed-down time ranges from 0.0s | ||
| to 3000.0s | ||
| DC brake | DC brake frequency: 0.00Hz ~ maximum frequency; brake time: 0.0s ~ 36.0s, and brake current value: 0.0% to 100.0%. | |
| Jog control | Jog frequency range:0.00Hz ~ 50.00Hz; | |
| Jog speed-up/speed-down time: 0.0s ~ 3000.0s. | ||
| Simple PLC and multi-speed running | It can realize a maximum of 16 segments speed running via the built-in PLC or control terminal. | |
| Built-in PID | It is easy to realize process-controlled close loop control system. | |
| (AVR)Automatic | It can keep constant output voltage automatically in case of change of mains voltage. | |
| voltage regulation | ||
| Torque limit and control | “Shovel” characteristics, automatic limit on the torque on running time, preventing frequent over-current trip; closed loop vector mode can realize the torque control | |
| Customized fuctions | Peripherals self-detection upon | It can conduct safety detections on the peripherals upon power-on, including earth and short circuit detections. |
| power-on | ||
| Shared DC bus | It can realize the function that multiple inverters share the DC bus. | |
| function | ||
| JOG key | Programmable key: Select the forward and reverse rotations/jog operation command. | |
| Customized fuctions | Traverse frequency control | Multiple triangular-wave frequency control function. |
| Fast current limit function | With fast current limit algorithm built in to reduce the probability of over-current alarm; to improve the anti-jamming capacity of the whole machine. | |
| Timed control | Timing control function: Setting time range from 0h to 65535h. | |
| Keyboard extension line standardization | Customers can use standard cable to extend the keyboard | |
| Operation function | Running command | Three types of channels: operation panel given, control terminal given and serial communication port given. These channels can be switched in various ways. |
| channel | ||
| Frequency source | Ten types of frequency sources in total: digital given, analog voltage given, analog current given, pulse given, and serial port given. It can be switched in various ways. | |
| Auxiliary frequency source | Ten types of auxiliary frequency sources in total. It can implement micro tuning and synthesis of auxiliary frequency. | |
| Input terminal | Five digital input terminals, and seven terminals in maximum (AI1, AI2 can be used as DI terminals), it has compatibility to PNP or NPN input method. | |
| Two analog input terminals, in which AI1 only be used for voltage input, and AI2 can be used as voltage or current input. (if expanded- input or output terminal function is needed, please use M700 series.) | ||
| Output terminal | One digital output terminal (bipolar output) | |
| Two relay output terminal | ||
| Two analog output terminals, with optional 0/4mA to 20mA or 0/2V to 10V. It can realize the output of set frequency, output frequency and rotation speed etc. | ||
| Display and Keyboard Operate | LED display | Display parameter |
| LCD display | Selective parts, Chinese/English to suggest the operation content | |
| Parameter copy | Use parameter special copy keyboard can copy the parameter quickly | |
| Key lock and function choose | Lock part of the keyboard or the whole keyboard, definite the function range of some keys to avoid mis-operation. | |
| Protection and select accessories | protection function | Short circuit detective of power-on motor, input and output open-phase protection, over-current protection, overvoltage protection, under-voltage protection, over-heat protection, over-load protection etc. |
| Selective accessories | LCD operation panel, brake group etc. | |
| Environment | Suitable place | Indoor environment which is against from direct sunlight, dust, corrosive gas, combustible gas, oil mist, vapor, water drop and salt. |
| Altitude | Less than 1000m | |
| Ambient Temperature | -10ºC ~ +50ºC (derating is required if the natural temperature range is 40ºC ~ 50ºC) | |
| Humidity | Less than 95%RH, no condensing water drops | |
| Vibration | Less than 5.9m/ s2 (0.6g) | |
| Storage temperature | -20ºC ~ +60ºC | |
| Class of pollution | 2 | |
| Product | Safety standard | IEC61800-5-1:2007 |
| standard | EMC standard | IEC61800-3:2005 |